• Sensorsoft Real Time Voltage & Contact Sensor (Ethernet)

The Sensorsoft Real-Time Contact and Voltage Sensor (SS6420) has 15 Boolean inputs that allow you to connect and monitor, in real-time, the state of dry contact based sensors and voltage sources. It also includes two relay outputs (SPDT) for controlling low voltage actuator loads such as lamps, audible alarms or solenoids. The SS6420 is housed in a mountable plastic module with screw terminal strips where external dry-contact security devices, voltage sources and actuator loads can be connected. The SS6420 communicates with the monitoring host/software over an RS232 serial port or 10/100 Base-T Ethernet interface.

Applications for the SS6420 include, but are not limited to monitoring/controlling the following:
•motion, glass-break and door sensors for physical security and activity
•smoke and fire detectors/systems
•diesel generators activity
•gas leak detectors
•AC power supplies or battery voltages
•door strike or lock solenoid
•door chimes and buzzers
•photocell detection of room lighting
•dry contact monitoring

The SS6420 is based on the Sensorsoft Device Protocol (Version 3.0) and includes protocol enhancements that immediately detect and report a state change on any of its dry-contact monitor inputs. For this reason you will know immediately when a door closes or a motion sensor triggers without waiting for a polling interval. The SS6420 works with Sensorsoft Remote Watchman Enterprise software. You can also develop your own software for the SS6420 using our Simple Text Command interface or our free Windows developer tools.

Similar to alarm panels, the SS6420 has a peripheral DC power supply for dry contact based detectors or actuator loads that require such to operate (i.e. motion sensors, smoke detectors, solenoids). This supply voltage is made available through screw terminals.

Two models of the SS6420 are available. The lower cost RS232 model (SS6420J) is powered by the serial interface from the RTS and DTR lines. It can be located up to 80 feet (24 m) from the serial port (depends on serial port) without the need for extenders or amplifiers. The Ethernet model (SS6420E) with its 10/100 Base-T interface has the advantage of direct IP connectivity without the need for a separate IP based device server. The SS6420E is supplied with a AC-DC mains power adapter or PoE adapter.

User Manual

General Features
•Monitor up to 12 dry contacts simultaneously
•Monitor up to 3 voltage sources with optical isolation
•Supports Sensorsoft Device Protocol (SSDP) or Simple Text Commands
•Provides 2 SPDT relays controllable by software
•Detects real-time pulses as short as 60 mS
•Responds to real-time state changes within 300 mS
•Option to filter out unwanted short pulses
•Terminals to distribute power to external peripheral devices
•Operates in polled or real-time mode
•Custom Boolean state strings and descriptions can be assigned to each input
•Serial RS232 model (SS6420J) does not require a power supply to operate *
•Ethernet model provides direct IP connectivity (no device server required)
•All power supplies protected by self-healing fuses
•Works with our full line of dry-contact security and safety detectors

SPECIFICATION


Electronic

Total Number of Monitored Inputs: 15
 (12 - contact inputs, ground referenced, numbered C1-C12)
 (3 - opto-isolated voltage inputs, not ground referenced, numbered V1-V3)
Total Number of Controlled Outputs: 2
 (2 - SPDT electromagnetic relay contacts (NO, NC, COM), numbered RL1 and RL2)
Screw Terminal Connectors: 8 connectors x 6 polls/connector (48 poles total), 3.50 mm pluggable screw-down connector, AWG 16-24, Molex P/N 39351-0006.
Relay contact load rating (RL1 or RL2): 1.5 Amp at 30 VDC
Maximum relay contact operating voltage (RL1-RL2): 30 VDC
Maximum relay contact operating current (RL1-RL2): 1.5 Amp
Maximum relay contact switching capacity (RL1-RL2): 62.5 VA, 33 W
Detection Method - Contact Inputs (C1-C12): Input transistor circuit detects external resistance between input and ground terminals. External resistances below 15K ohm produce a CLOSED condition/state. External resistances above 600K ohm produce an OPEN condition/state.
Input Resistance of Opto-isolated Voltage Inputs (V1-V3): 16K Ohm
Detection Method - Opto-isolated Voltage Inputs (V1-V3): Optical coupler detects voltage difference between V+ and V-. A voltage difference, on these terminals, below approximately 3 volts produces an OFF condition/state. A voltage difference, on these terminals, equal to or greater than approximately 3 volts produces an ON condition/state. The minimum recommended voltage input for an ON condition/state is dependent upon resistance of the voltage source.
Minimum Detectable Input Duration: 60 mS. This specification is not valid during a write to any variable in the SS6420’s non-volatile memory.
Maximum Time from State Change to Issue of Interrupt Packet: 300 mS. This specification is not valid during a write to any variable in the SS6420’s non-volatile memory.
Maximum Applied Voltage on Opto-isolated Voltage Inputs (V1-V3): 30 V
Power source: External AC-DC power adapter
Power supply current drain: < 300 mA
External Power Source Connector: 2.1 mm jack
External Power Source Requirements: 6 VDC, 300 mA capability (input circuit is polarity protected). Recommended power adapter is P/N PA6106.
Peripheral DC Power Source: for external peripheral devices
Peripheral Power Source Connector: 2.5 mm jack
Peripheral Power Source Requirements: Center negative (input circuit is polarity protected). The input DC voltage will depend on the requirements of peripheral devices that the customer is powering. The maximum input voltage allowed is 30 VDC. The maximum current that can be conducted is 0.75 Amp after which the internal overload protection will trigger. The overload protection is provided by a self-healing poly-fuse. This power source is made available through 12 polls of the screw terminal connectors. The recommended power adapter for powering security detectors is P/N PA6420-XX (12 VDC, 1.2 A).
 

Software Interface

Communications Interface: 10/100 Base-T Ethernet
Communications Connector: 8 position modular jack, (accepts 8 position plug, RJ45)
Maximum communications cable length: 100 m (328 ft.) using appropriate UTP cable.
Transport Layer Communications Protocol: TCP
IP Address: defined by customer (can be dynamic via DHCP or static, default is DHCP)
TCP Port Number: defined by customer (default is 3001)
Firmware Version: 5.08
Application Layer Communications Protocols: Sensorsoft Device Protocol (SSDP) Version 3.0 or Simple Text Command Interface (see User Manual for commands)
Communications Error Control:  (SSDP only) 16 bit CRC (cyclic redundancy checking) for detection of communication errors between the device and host.
Number of Variables: 87
EEPROM: 2 Kbytes. Stores user defined input description and Boolean state strings
Maximum Length of Input Description String: 32 characters
Maximum Length of Boolean State String: 8 characters
 

Physical

Housing Dimensions: 7.5” (190 mm) x 2.8” (71 mm) x 1.1" (28 mm)
Housing Material: injection molded ABS thermoplastic
Housing Color: Grey
Operating Temperature Range: 0 º C to +60 º C (32 º F to +140 º F) - available for -40 º C to +60 º C range on special order
Operating Humidity Range: 90% or less, non-condensing

 



 



 

 

Write a review

Note: HTML is not translated!
    Bad           Good
Captcha

Sensorsoft Real Time Voltage & Contact Sensor (Ethernet)

  • Brand: Sensorsoft
  • Product Code: SS6420E
  • Availability: In Stock
  • £302.50


Related Products

AC-DC Power Adapter for SS6420 Peripheral Power Supply (12 VDC)

AC-DC Power Adapter for SS6420 Peripheral Power Supply (12 VDC)

This is required for the SS6420 if you use security detectors, solenoids or audible alarms that must..

£41.80

AC-DC Power Adapter (6 VDC)

AC-DC Power Adapter (6 VDC)

Required for Sensorsoft Ethernet devices SS8002 and SS6420E. CE marked. Input: Autoswitching 90-264 ..

£11.00